Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2018, 12:59 PM
  • Section#1_08 0005_08 0004__1232018__I0082.mp4

Date
12/03/2018
W/O
0741815
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00005
Time
4:59 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0082
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20181203MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0005
Downstream MH
08 0004
Dir. of Survey
Downstream
Length Surveyed
315.6 ft.
Total Length
315.6 ft.
Structural Index
5
Structural Quick
5L4K
Structural Rating
583
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
583
Pipe schematic from manhole 08 0005 to 08 0004
MH: 08 0005MH: 08 0004downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:25AM0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR2 ft. MGO - General Observation - MISSING TILES 100% 9:00 TO 3:008.2 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR14.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR33.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR86.9 ft. MGO - General Observation - 1 ROW TILES IN PLACE137.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR147.6 ft. MGO - General Observation - 1 ROW TILES IN PLACE283.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE304.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR312.6 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG312.6 ft. MGO - General Observation - MISSING TILES 100% FINISH312.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR315.6 ft. AMH - Downstream Manhole, Survey Ends - 6:05AM

Observation photos (9)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • General Observation - MISSING TILES 100% 9:00 TO 3:00

    2 ft. - General Observation - MISSING TILES 100% 9:00 TO 3:00

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    8.2 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    14.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    33.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • General Observation - 1 ROW TILES IN PLACE

    86.9 ft. - General Observation - 1 ROW TILES IN PLACE

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    137.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE

    283.5 ft. - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE

Observations (18)

DistanceCodeObservation
2SAMSEVERE AGG AREAS OF MISSING TILES
0MWL
86.9MGO1 ROW TILES IN PLACE
312.6SAMSEVERE AGG
14.6SRCCIRCUM REBAR
0AMH5:25AM
2SRCLONG CIRCUM REBAR
8.2SRCLONG REBAR
137.4SRCLONG & CIRCUM REBAR
283.5TFACTIVE
147.6MGO1 ROW TILES IN PLACE
0MWM
33.3SRCLONG & CIRCUM REBAR
315.6AMH6:05AM
2MGOMISSING TILES 100% 9:00 TO 3:00
312.6MGOMISSING TILES 100% FINISH
312.6SRCLONG & CIRCUM REBAR
304.9SRCLONG CIRCUM REBAR

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2018-12-03T04:59:22-08:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false