Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2017, 10:08 AM
  • 01 1186_01 1185_04142017_030918.mp4

Date
04/14/2017
W/O
630364
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00225
PipeID
P02040
Time
3:08 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4429
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
WO_630364_TV01257_APR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1186
Downstream MH
01 1185
Dir. of Survey
Downstream
Length Surveyed
257.3 ft.
Total Length
257.3 ft.
Structural Index
3
Structural Quick
3J2I
Structural Rating
257
O&M Index
2
O&M Quick
2I00
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
359
Pipe schematic from manhole 01 1186 to 01 1185
MH: 01 1186MH: 01 1185downstream0 ft. MGO - General Observation - ACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11860 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start56.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"66.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.4 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES137.9 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES146.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.2 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"185.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.6 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"225.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"228.5 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"255.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish255.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish257.3 ft. AMH - Downstream Manhole, Survey Ends - 01 1185257.3 ft. MGO - General Observation - ROACHES IN MH

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    109.4 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    137.9 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
0MGOACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK
2DAGS
0MWL
66.8TFA
187.6TFA
185.3TFA
0AMH01 1186
69.5TFA
257.3AMH01 1185
10.8SSS
146.9TFA
107.2TFA
137.9FL
109.4FL
56.6TFA
257.3MGOROACHES IN MH
228.5TFA
0MWM
109.3TFA
150.2TFA
255.5SAV
255.5DAGS
225.5TFA
2.1SAV
255.5SSS

Properties (6)

additional_info
SC307000
custom_field_two
2
customer
LACSD
datetime
2017-04-14T03:08:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false