Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2017, 08:34 AM
  • 29 0260_29 0259A _17032017_013513.mpg

Date
03/17/2017
W/O
624460
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24164
Time
1:34 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4383
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_624460_TV29035_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0260
Downstream MH
29 0259A
Dir. of Survey
Downstream
Length Surveyed
110.6 ft.
Total Length
110.6 ft.
Structural Index
2
Structural Quick
3212
Structural Rating
8
O&M Index
1
O&M Quick
311B
O&M Rating
18
Overall Index
1
Overall Quick
Overall Rating
26
Pipe schematic from manhole 29 0260 to 29 0259A
MH: 29 0260MH: 29 0259Adownstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 02600 ft. MWL - Water Level, 5 %of cross sectional area5.1 ft. CC - Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES10.2 ft. CC - Crack Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES10.2 ft. RFJ - Roots Fine Joint, from 10 to 04 o'clock, within 8 inches of joint: YES23.3 ft. RFJ - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES38.3 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES41.4 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES41.4 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES53.2 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start73 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"78.8 ft. RML - Roots Medium Lateral, at 02 o'clock, 20 %, within 8 inches of joint: NO78.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"103.9 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES110.6 ft. ACOM - Cleanout Mainline, Survey Ends - 29 0259A110.6 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    5.1 ft. - Crack Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES

    10.2 ft. - Crack Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 10 to 04 o'clock, within 8 inches of joint: YES

    10.2 ft. - Roots Fine Joint, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES

    23.3 ft. - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

    38.3 ft. - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

    41.4 ft. - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    41.4 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    53.2 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    103.9 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
78.8RML
41.4RFJ
10.2CC
5.1CC
0MWM
23.3RFJ
103.9CM
0AMH29 0260
53.2RFJ
0MWL
110.6ACOM29 0259A
10.2RFJ
41.4CM
110.6RFJ
73TFC
78.8TF
38.3RFJ

Properties (6)

additional_info
SC306892
custom_field_two
4
customer
LACSD
datetime
2017-03-17T01:34:04-07:00
documentation
PROPIPE
is_lateral_inspection
false