Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2018, 08:48 PM
  • 29 0416_29 0415_11282018_125154.mp4

Date
11/28/2018
W/O
0741915
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00355
PipeID
P24453
Time
12:48 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7864
Sewer Name
29 LEWIS AVENUE TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Maintenance Related
Project
20181128DF_LEWIS_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
7.679999828338623 in.
Upstream MH
29 0416
Downstream MH
29 0415
Dir. of Survey
Downstream
Length Surveyed
300.6 ft.
Total Length
300.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2311
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 29 0416 to 29 0415
MH: 29 0416MH: 29 0415downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:50 PM0 ft. MGO - General Observation - ROACHES @ MH97.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"97.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES97.4 ft. MGP - General Photograph138.5 ft. MGP - General Photograph174.7 ft. MGP - General Photograph202.3 ft. MGP - General Photograph207.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE/5% ROOTS IN LATERAL298.8 ft. RFC - Roots Fine Connection, at 10 o'clock, within 8 inches of joint: YES - 25% ROOTS300.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - 100% ROOTS/LATERAL300.6 ft. MSA - Survey Abandoned - ROOT MASS300.6 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (9)

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: YES

    97.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES

  • General Photograph

    97.4 ft. - General Photograph

  • General Photograph

    138.5 ft. - General Photograph

  • General Photograph

    174.7 ft. - General Photograph

  • General Photograph

    202.3 ft. - General Photograph

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE/5% ROOTS IN LATERAL

    207.9 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - ACTIVE/5% ROOTS IN LATERAL

  • Roots Fine Connection, at 10 o'clock, within 8 inches of joint: YES - 25% ROOTS

    298.8 ft. - Roots Fine Connection, at 10 o'clock, within 8 inches of joint: YES - 25% ROOTS

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - 100% ROOTS/LATERAL

    300.5 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4" - 100% ROOTS/LATERAL

Observations (15)

DistanceCodeObservation
300.6MSAROOT MASS
300.5TFD100% ROOTS/LATERAL
298.8RFC25% ROOTS
97.4TFA
207.9TFDACTIVE/5% ROOTS IN LATERAL
97.4DAGS
0MWM
0MWL
202.3MGP
0AMH12:50 PM
138.5MGP
174.7MGP
300.6MGOGREASE THROUGHOUT THE REACH (5%)
97.4MGP
0MGOROACHES @ MH

Properties (6)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2018-11-28T12:48:26-08:00
documentation
FRANKLIN, IGNACIO, CASTILLO, RUVALCABA
is_lateral_inspection
false
lining
CIPP