Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 27, 2018, 09:11 PM
  • 22 1015_22 1014_11272018_131840.mp4

Date
11/27/2018
W/O
0738900
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00819
PipeID
P17384
Time
1:11 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
G7863
Sewer Name
22 LORAINE TRUNK
City
GLENDORA
Loc. details
Building
Location Code
J
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Maintenance Related
Project
20181127DF_PUDDINGSTONE_TRUNK_SECTS_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 1015
Downstream MH
22 1014
Dir. of Survey
Downstream
Length Surveyed
373.6 ft.
Total Length
373.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4222
O&M Rating
13
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 22 1015 to 22 1014
MH: 22 1015MH: 22 1014downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:16 PM2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG18.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"72.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"148.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"185 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"221.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"265.5 ft. MGP - General Photograph - 15% OUR LINE265.5 ft. RBL - Roots Ball Lateral, at 02 o'clock, 100 %, within 8 inches of joint: YES - 100% ROOTS LATERAL265.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN313.2 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 5%316.7 ft. MGP - General Photograph316.7 ft. RTJ - Roots Tap Joint, from 07 to 09 o'clock, 5 %, within 8 inches of joint: YESR322.4 ft. RBL - Roots Ball Lateral, at 02 o'clock, 100 %, within 8 inches of joint: YES322.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 100% ROOTS LATERAL349.1 ft. MGP - General Photograph349.1 ft. RTJ - Roots Tap Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR373.5 ft. MGP - General Photograph373.5 ft. MGP - General Photograph373.5 ft. MGP - General Photograph373.6 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG373.6 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach373.6 ft. MGO - General Observation - Grease Throughout The Reach (5%)373.6 ft. MSA - Survey Abandoned - ROOT MASS

Observation photos (14)

  • Water Mark, 30 %of cross sectional area

    0 ft. - Water Mark, 30 %of cross sectional area

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG

  • General Photograph - 15% OUR LINE

    265.5 ft. - General Photograph - 15% OUR LINE

  • Roots Ball Lateral, at 02 o'clock, 100 %, within 8 inches of joint: YES - 100% ROOTS LATERAL

    265.5 ft. - Roots Ball Lateral, at 02 o'clock, 100 %, within 8 inches of joint: YES - 100% ROOTS LATERAL

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 5%

    313.2 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR - 5%

  • General Photograph

    316.7 ft. - General Photograph

  • Roots Tap Joint, from 07 to 09 o'clock, 5 %, within 8 inches of joint: YESR

    316.7 ft. - Roots Tap Joint, from 07 to 09 o'clock, 5 %, within 8 inches of joint: YESR

  • Roots Ball Lateral, at 02 o'clock, 100 %, within 8 inches of joint: YES

    322.4 ft. - Roots Ball Lateral, at 02 o'clock, 100 %, within 8 inches of joint: YES

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 100% ROOTS LATERAL

    322.4 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 100% ROOTS LATERAL

  • General Photograph

    349.1 ft. - General Photograph

  • Roots Tap Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR

    349.1 ft. - Roots Tap Joint, from 04 to 05 o'clock, 5 %, within 8 inches of joint: YESR

  • General Photograph

    373.5 ft. - General Photograph

  • General Photograph

    373.5 ft. - General Photograph

  • General Photograph

    373.5 ft. - General Photograph

Observations (26)

DistanceCodeObservation
2SZ65% MAG
349.1MGP
316.7MGP
373.6SZ65% MAG
221.5TFC
373.6MGOPeeling & Flaking Throughout The Reach
18.5TFA
265.5MGP15% OUR LINE
0MWM
265.5RBL100% ROOTS LATERAL
313.2RFJ5%
373.6MGOGrease Throughout The Reach (5%)
373.5MGP
316.7RTJ
148.9TF
72.1TF
0MWL
185TFA
373.5MGP
265.5TFOPEN
349.1RTJ
0AMH1:16 PM
373.5MGP
322.4RBL
322.4TFA100% ROOTS LATERAL
373.6MSAROOT MASS

Properties (4)

customer
LACSD
datetime
2018-11-27T13:11:13-08:00
documentation
FRANKLIN, IGNACIO, CASTILLO, RUVALCABA
is_lateral_inspection
false