Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 27, 2018, 11:20 AM
  • 18 0467_18 0466_11272018_033553.mp4

Date
11/27/2018
W/O
O740960
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00691
PipeID
P14321
Time
3:20 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1062
Sewer Name
18 NORTH PLANT OUTFALL TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20181126MDM_NORTH_PLANT_OUTFALL_TRUNK
Material
NRCP
Shape
Circular
Height
21 in.
Upstream MH
18 0467
Downstream MH
18 0466
Dir. of Survey
Downstream
Length Surveyed
278.5 ft.
Total Length
278.5 ft.
Structural Index
5
Structural Quick
5A41
Structural Rating
61
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
61
Pipe schematic from manhole 18 0467 to 18 0466
MH: 18 0467MH: 18 0466downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:20AM0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:0011.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open17.5 ft. SRC - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR30.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR31.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR38.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Finish - LONG CIRCUM REBAR43.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active59.1 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR69.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open94.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open101.7 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR115.1 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR122.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open124.5 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR130.5 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR131.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR134.2 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Finish - CIRCUM REBAR145.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open147.9 ft. SRC - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR172.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR192.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR236.1 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR278 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG278 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PELLING CONCRETE SEVERE AGG ATTACHED278 ft. MGO - General Observation - MAG COAT 80% FINISH278.5 ft. AMH - Downstream Manhole, Survey Ends - 3:55AM

Observation photos (14)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 80% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 80% START 9:00 TO 3:00

  • Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    17.5 ft. - Surface Reinforcement Corroded, from 02 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    30.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR

    31.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    59.1 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    101.7 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

    124.5 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    130.5 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    131.9 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    147.9 ft. - Surface Reinforcement Corroded, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    172.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    236.1 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (31)

DistanceCodeObservation
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
38.3SRCLONG CIRCUM REBAR
0MWM
147.9SRCCIRCUM REBAR
278SAMSEVERE AGG
172.1SRCCIRCUM REBAR
43.1TFActive
122.1TFOpen
31.3SRCLONG CIRCUM REBAR
17.5SRCCIRCUM REBAR
145.4TFOpen
59.1SRCCIRCUM REBAR
69.3TFOpen
192.2SRCCIRCUM REBAR
30.6SRCLONG & CIRCUM REBAR
124.5SRCCIRCUM REBAR
278SSSBLISTERING PELLING CONCRETE SEVERE AGG ATTACHED
0AMH3:20AM
131.9SRCCIRCUM REBAR
278MGOMAG COAT 80% FINISH
101.7SRCCIRCUM REBAR
130.5SRCCIRCUM REBAR
2SAMSEVERE AGG
134.2SRCCIRCUM REBAR
0MWL
94.6TFOpen
236.1SRCCIRCUM REBAR
115.1SRCCIRCUM REBAR
2MGOMAG COAT 80% START 9:00 TO 3:00
11.2TFOpen
278.5AMH3:55AM

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2018-11-27T03:20:00-08:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false