Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2018, 05:59 AM
  • 15 0588_15 0587 _26062018_230721.mp4

Date
06/26/2018
W/O
712422
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00613
PipeID
P12518
Time
10:59 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5756
Sewer Name
15 LOWER AZUSA ROAD TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
WO_712422_TV15234_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0588
Downstream MH
15 0587
Dir. of Survey
Downstream
Length Surveyed
230.2 ft.
Total Length
230.2 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
138
Pipe schematic from manhole 15 0588 to 15 0587
MH: 15 0588MH: 15 0587downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 05880 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 10 %of cross sectional area2.4 ft. MGO - General Observation - MAG COAT2.6 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start24.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"60.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"190 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK230.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0587230.2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
230.2MGOCONNECTION AT MH 9 O'CLOCK
2.4MGOMAG COAT
230.2AMH15 0587
0AMH15 0588
230.2SAV
2.6SAV
0MWL
190TFC
0MGOCONNECTION AT MH 9 O'CLOCK
60.1TFC
0MGOCONNECTION AT MH 3 O'CLOCK
153.7TFC
0MWM
24.6TF

Properties (4)

additional_info
SC359665
custom_field_two
3
customer
LACSD
datetime
2018-06-26T22:59:15-07:00