Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2018, 11:22 AM
  • 32 0027_32 0026A _29062018_043446.mp4

Date
06/29/2018
W/O
712174
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00886
PipeID
P24256
Time
4:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5755
Sewer Name
32 CASTAIC TRUNK
City
CASTAIC
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
03
Purpose
Routine Assessment
Project
WO_712174_TV32055_JUL2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 0027
Downstream MH
32 0026A
Dir. of Survey
Downstream
Length Surveyed
148.3 ft.
Total Length
148.3 ft.
Structural Index
3
Structural Quick
3C21
Structural Rating
62
O&M Index
2
O&M Quick
2E00
O&M Rating
58
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 32 0027 to 32 0026A
MH: 32 0027MH: 32 0026Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 00270 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start40.8 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES47.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start148.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish148.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish148.3 ft. AMH - Downstream Manhole, Survey Ends - 32 0026A

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    40.8 ft. - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    47.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH32 0027
47.4CM
148.3CM
40.8CS
0MWM
2DAGS
148.3DAGS
148.3AMH32 0026A
0MGOCAPPED CONNECTION AT MH 3 O'CLOCK
0MWL

Properties (4)

additional_info
SC359721
custom_field_two
3
customer
LACSD
datetime
2018-06-29T04:22:41-07:00