Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 3, 2018, 08:23 AM
  • 02 0892_02 0891 _03072018_014608.mp4

Date
07/03/2018
W/O
712060
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00249
PipeID
P03461
Time
1:23 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4004
Sewer Name
02 DOWNEY TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Maintenance Related
Project
WO_712060_TV02050_JUL2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0892
Downstream MH
02 0891
Dir. of Survey
Downstream
Length Surveyed
305.9 ft.
Total Length
305.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0892 to 02 0891
MH: 02 0892MH: 02 0891downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 08920 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"87.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"90.2 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR119.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"141.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"172.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"196.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"242.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"303.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish303.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish305.4 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH305.7 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT305.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0891

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

    90.2 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

Observations (18)

DistanceCodeObservation
141.4TF
90.2RFJ
2.1DAGS
87.2TB
305.4MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
39.8TF
305.7MGOCAPPED CONNECTION AT 9 O' CLOCK AT
119.9TB
303.4DAGS
0AMH02 0892
172.3TB
242.8TF
305.9AMH02 0891
196.2TB
0MWM
0MWL
2.1SAV
303.4SAV

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2018-07-03T01:23:04-07:00