Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2018, 06:00 AM
  • 18 0870_18 0868 _03072018_155332.mp4

Date
06/14/2018
W/O
707024
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00709
PipeID
P14721
Time
11:00 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5198
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
WO_707024_TV18101_JUN2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0870
Downstream MH
18 0868
Dir. of Survey
Downstream
Length Surveyed
584.9 ft.
Total Length
584.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4125
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole 18 0870 to 18 0868
MH: 18 0870MH: 18 0868downstream0 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MAGNEZIUM H.O COATING0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08700 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH13.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start94.2 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.6 ft. MGO - General Observation - MAG COATING FLAKING302.8 ft. LL - Alignment Left, 20 %, Start448.3 ft. LL - Alignment Left, 20 %, Finish462.8 ft. LR - Alignment Right, 20 %, Start483.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"583.9 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish583.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish583.9 ft. LR - Alignment Right, 20 %, Finish584.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0868584.9 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (4)

  • Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start - MAGNEZIUM H.O COATING

    0 ft. - Deposits Attached Other, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start - MAGNEZIUM H.O COATING

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    13.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Alignment Left, 20 %, Start

    302.8 ft. - Alignment Left, 20 %, Start

  • Alignment Right, 20 %, Start

    462.8 ft. - Alignment Right, 20 %, Start

Observations (17)

DistanceCodeObservation
448.3LL
302.8LL
167.6MGOMAG COATING FLAKING
13.3DAGS
94.2TBC
583.9DAZ
0DAZMAGNEZIUM H.O COATING
0MWL
0AMH18 0870
584.9AMH18 0868
0MWM
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
584.9MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
483.5TFC
583.9DAGS
583.9LR
462.8LR