22 0709A_22 0709 _11052018309_213236.mp4
2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start
2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start
4.2 ft. - Fracture Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES
8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start
139.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES
161.1 ft. - General Observation - COCKROACHES IN MANHOLE
| Distance | Code | Observation |
|---|---|---|
| 162.5 | AMH | 22 0709 |
| 0 | AMH | 22 0709A |
| 0 | MWM | — |
| 0 | MGO | ACTIVE CONNECTION AT MH 9 O'CLOCK |
| 161.1 | MGO | COCKROACHES IN MANHOLE |
| 161.1 | SSS | — |
| 4.2 | FM | — |
| 161.1 | DAGS | — |
| 2 | DAGS | — |
| 8 | SSS | — |
| 0 | MWL | — |
| 161.1 | SAP | — |
| 139.5 | FM | — |
| 107.6 | TFC | — |
| 2 | SAP | — |