Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 5, 2018, 11:31 AM
  • 22 0705_22 0704 _11052018309_033153.mp4

Date
11/05/2018
W/O
735127
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00826
PipeID
P17058
Time
3:31 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6195
Sewer Name
22 SAN DIMAS CONNECTION EXTENSION TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_735127_TV22167_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0705
Downstream MH
22 0704
Dir. of Survey
Downstream
Length Surveyed
407.2 ft.
Total Length
407.2 ft.
Structural Index
3
Structural Quick
3P2O
Structural Rating
414
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
576
Pipe schematic from manhole 22 0705 to 22 0704
MH: 22 0705MH: 22 0704downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 07050 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start32.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"60.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES177.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.1 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"231.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start353.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish405.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish405.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish407.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE407.2 ft. AMH - Downstream Manhole, Survey Ends - 22 0704

Observation photos (7)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    164.7 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    349.3 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    407.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (23)

DistanceCodeObservation
405.3DAGS
0AMH22 0705
407.2MGOCOCKROACHES IN MANHOLE
2DAGS
278.1TB
164.7FL
0MWM
32.8TFC
0MGOCOCKROACHES IN MANHOLE
349.3FL
177.7TFC
405.3SAP
407.2AMH22 0704
353.6FL
0MWL
2SSS
285.6TFC
181.1TBA
60.2TFC
324.9TFC
405.3SSS
2SAP
231.6TF

Properties (4)

additional_info
SC365361
custom_field_two
2
customer
LACSD
datetime