- Date
- 11/05/2018
- W/O
- 735036
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00831
- PipeID
- P16727
- Time
- 1:25 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K6194
- Sewer Name
- 22 WALNUT CREEK TRUNK, SECTION 3
- City
- COVINA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 22
- Page No.
- 33
- Purpose
- Routine Assessment
- Project
- RFIR_WO_735036_TV22065_NOV2018
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 22 0393
- Downstream MH
- 22 0392
- Dir. of Survey
- Downstream
- Length Surveyed
- 303 ft.
- Total Length
- 303 ft.
- Structural Index
- 3
- Structural Quick
- 3K2I
- Structural Rating
- 276
- O&M Index
- 2
- O&M Quick
- 2K12
- O&M Rating
- 122
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 398
Pipe schematic from manhole 22 0393 to 22 0392 Observation photos (5)

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

63 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

245.5 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR

251 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR