Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2018, 12:31 PM
  • 02 1758A_02 1758_11162018_043554.mp4

Date
11/16/2018
W/O
0739479
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00254
PipeID
P04104
Time
4:31 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1055R
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Maintenance Related
Project
20181116MDM_DOWNEY_BELLFLOWER_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
02 1758A
Downstream MH
02 1758
Dir. of Survey
Downstream
Length Surveyed
74.6 ft.
Total Length
74.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1758A to 02 1758
MH: 02 1758AMH: 02 1758downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:35AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open18.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open22.9 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YESR - 1%54.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open74 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish74 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped74.6 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
18.8TFOpen
22.9RFJ1%
6.5TFOpen
54.7TFOpen
0AMH4:35AM
0MWL
74DAGS
74MGOConn. @ Mh, 3 O' Clock. Capped
0MGOConn. @ Mh, 9 O' Clock. Active
74.6AMH4:45AM
2DAGS
0MWM

Properties (4)

customer
LACSD
datetime
2018-11-16T04:31:16-08:00
documentation
MARTIN,REVELEVES,OLIVER 111,BRAR
is_lateral_inspection
false