Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2018, 11:36 AM
  • 02 1759A_02 1759_11162018_033936.mp4

Date
11/16/2018
W/O
0739479
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00254
PipeID
P04106
Time
3:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1055R
Sewer Name
02 DOWNEY-BELLFLOWER EXTENSION TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
15
Purpose
Maintenance Related
Project
20181116MDM_DOWNEY_BELLFLOWER_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
02 1759A
Downstream MH
02 1759
Dir. of Survey
Downstream
Length Surveyed
201.7 ft.
Total Length
201.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 1759A to 02 1759
MH: 02 1759AMH: 02 1759downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:45AM0 ft. MWM - Water Mark, 20 %of cross sectional area0.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open85.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Open130.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active201.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish201.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped201.2 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active201.7 ft. AMH - Downstream Manhole, Survey Ends - 4:00AM

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
7.5TFOpen
201.7AMH4:00AM
0MGOConn. @ Mh, 3 O' Clock. Active
85.5TBOpen
0MWL
201.2DAGS
201.2MGOConn. @ Mh, 3 O' Clock. Capped
130.2TFActive
0AMH3:45AM
201.2MGOConn. @ Mh, 9 O' Clock. Active
0.8DAGS
0MWM

Properties (4)

customer
LACSD
datetime
2018-11-16T03:36:11-08:00
documentation
MARTIN,REVELEVES,OLIVER 111,BRAR
is_lateral_inspection
false