Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2018, 08:24 AM
  • 05 1686_05 1685_11132018_011249.mp4

Date
11/13/2018
W/O
O734333
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06915
Time
12:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1049
Sewer Name
05 LOMITA TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20181113MDM_LOMITA_TRUNK
Material
CIP
Shape
Circular
Height
16 in.
Upstream MH
05 1686
Downstream MH
05 1685
Dir. of Survey
Downstream
Length Surveyed
7.5 ft.
Total Length
7.5 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
5
O&M Quick
5200
O&M Rating
10
Overall Index
4
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 1686 to 05 1685
MH: 05 1686MH: 05 1685downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active-OUTGOING0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SCP - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: YES, Change - 10% MISSING PIPE5 ft. SCP - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: NO - 30% MISSING PIPE7 ft. MGP - General Photograph7 ft. DSZ - Deposits Settled Other, 90 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: NO - SLUDGE PAPER7.5 ft. MSA - Survey Abandoned - 90% SLUDGE

Observation photos (4)

  • Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: YES, Change - 10% MISSING PIPE

    2 ft. - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: YES, Change - 10% MISSING PIPE

  • Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: NO - 30% MISSING PIPE

    5 ft. - Surface Corrosion Metal Pipe, from 10 to 02 o'clock, within 8 inches of joint: NO - 30% MISSING PIPE

  • General Photograph

    7 ft. - General Photograph

  • Deposits Settled Other,  90 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: NO - SLUDGE PAPER

    7 ft. - Deposits Settled Other, 90 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: NO - SLUDGE PAPER

Observations (9)

DistanceCodeObservation
0AMH12:55AM
0MWM
2SCP10% MISSING PIPE
5SCP30% MISSING PIPE
0MGOConn. @ Mh, 9 O' Clock. Active-OUTGOING
7MGP
0MWL
7.5MSA90% SLUDGE
7DSZSLUDGE PAPER

Properties (4)

customer
LACSD
datetime
2018-11-13T00:24:48-08:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false