Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2018, 03:59 PM
  • 03 0622_03 0621_1192018_080157.mp4

Date
11/09/2018
W/O
0662165
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00389
PipeID
P22205
Time
7:59 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7849
Sewer Name
03 NORTH LONG BEACH RELIEF TRUNK
City
LONG BEACH
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
18
Purpose
Routine Assessment
Project
20181109DF_NORTH_LONG_BEACH_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Upstream MH
03 0622
Downstream MH
03 0621
Dir. of Survey
Downstream
Length Surveyed
162.8 ft.
Total Length
162.8 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
3
O&M Quick
4133
O&M Rating
19
Overall Index
3
Overall Quick
Overall Rating
32
Pipe schematic from manhole 03 0622 to 03 0621
MH: 03 0622MH: 03 0621downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 7:59 AM0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29 ft. MGP - General Photograph35 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES35.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES40.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES48 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES111.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES117.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES147.4 ft. IR - Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES147.4 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES147.4 ft. MGP - General Photograph - RUNNER159.4 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES160 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish162.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish162.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish162.8 ft. AMH - Downstream Manhole, Survey Ends - 8:28 AM162.8 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (13)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    29 ft. - General Photograph

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    35 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    35.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    40.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    48 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    111.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    117.8 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES

    147.4 ft. - Infiltration Runner, at 11 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES

    147.4 ft. - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES

  • General Photograph - RUNNER

    147.4 ft. - General Photograph - RUNNER

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

    159.4 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
29MGP
35ID
147.4IR
2DAGS
162.8AMH8:28 AM
111.8CL
48DAGS
162.4CM
159.4ID
2SSS
2CM
162.4SSS
160DAGS
117.8DAE
35.1CM
0MWM
0AMH7:59 AM
147.4ID
0MWL
147.4MGPRUNNER
40.9CM
162.8MGOGREASE THROUGHOUT THE REACH (5%)

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2018-11-09T07:59:39-08:00
documentation
FRANKLIN, CASTILLO, RUVALCABA, YOUNG
is_lateral_inspection
false