Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 12, 2018, 04:12 PM
  • H 0510_H 0509_12102018_091431.mp4

Date
10/12/2018
W/O
729980
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00183
PipeID
P10936
Time
9:12 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5915
Sewer Name
H JOINT OUTFALL H - UNIT 7B
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
RFIR_WO_729980_TV15231_OCT2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
45 in.
Width
45 in.
Upstream MH
H 0510
Downstream MH
H 0509
Dir. of Survey
Downstream
Length Surveyed
481.3 ft.
Total Length
481.3 ft.
Structural Index
3
Structural Quick
3R00
Structural Rating
285
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
285
Pipe schematic from manhole H 0510 to H 0509
MH: H 0510MH: H 0509downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 05100 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area5.9 ft. MGO - General Observation - MAG COAT6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start228 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 10"358.2 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 12"363.2 ft. MGO - General Observation - UNMAPPED MANHOLE481.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish481.3 ft. AMH - Downstream Manhole, Survey Ends - H 0509

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COAT

    5.9 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 10"

    228 ft. - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 10"

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 12"

    358.2 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 12"

  • General Observation - UNMAPPED MANHOLE

    363.2 ft. - General Observation - UNMAPPED MANHOLE

Observations (11)

DistanceCodeObservation
481.2SAP
481.3AMHH 0509
0AMHH 0510
5.9MGOMAG COAT
6SAP
358.2TB
0MGOCOCKROACHES IN MANHOLE
228TF
363.2MGOUNMAPPED MANHOLE
0MWM
0MWL

Properties (4)

additional_info
SC365115
custom_field_two
2
customer
LACSD
datetime
2018-10-12T09:12:24-07:00