Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 11, 2018, 06:30 AM
  • 02 1822_02 1821 _10102018_233029.mp4

Date
10/10/2018
W/O
729453
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00236
PipeID
P04169
Time
11:30 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6143
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_729453_TV02017_OCT2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1822
Downstream MH
02 1821
Dir. of Survey
Downstream
Length Surveyed
292.5 ft.
Total Length
292.5 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
290
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 02 1822 to 02 1821
MH: 02 1822MH: 02 1821downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 18220 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start292.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1821292.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish292.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
292.5AMH02 1821
0MGOCONNECTION AT MH 9 O'CLOCK
0AMH02 1822
3SAP
0MWM
292.5SSS
0MWL
3SSS
292.5SAP

Properties (4)

additional_info
SC365210
custom_field_two
2
customer
LACSD
datetime
2018-10-10T23:30:01-07:00