Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2017, 09:15 AM
  • 18 0194_18 0193 _20170331_025633.mp4

Date
03/31/2017
W/O
624437
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00695
PipeID
P14019
Time
2:15 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4337
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0194
Downstream MH
18 0193
Dir. of Survey
Downstream
Length Surveyed
433 ft.
Total Length
433 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0194 to 18 0193
MH: 18 0194MH: 18 0193downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01940 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 30%4.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start433 ft. AMH - Downstream Manhole, Survey Ends - 18 0193433 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish433 ft. MGO - General Observation - CONNECTION AT 9 OC

Observations (8)

DistanceCodeObservation
0MWL
433AMH18 0193
433DAGS
0AMH18 0194
4.8DAGS
0MWM
433MGOCONNECTION AT 9 OC
2MGOMAG COAT 30%

Properties (5)

additional_info
SC340702
custom_field_two
4
customer
LACSD
datetime
2017-03-31T02:15:32-07:00
is_lateral_inspection
false