Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 30, 2016, 06:39 AM
  • 21 0325_21 0324_29122016_224351.mpg

Date
12/29/2016
W/O
613609
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00763
PipeID
P15522
Time
10:39 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4110
Sewer Name
21 DISTRICT #21 OUTFALL TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
14
Purpose
Routine Assessment
Project
WO_613609_TV21044_JAN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
21 0325
Downstream MH
21 0324
Dir. of Survey
Downstream
Length Surveyed
59.1 ft.
Total Length
59.1 ft.
Structural Index
4
Structural Quick
5A3A
Structural Rating
83
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
83
Pipe schematic from manhole 21 0325 to 21 0324
MH: 21 0325MH: 21 0324downstream0 ft. AMH - Upstream Manhole, Survey Begins - 21 03250 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area6.6 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start7.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.1 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish59.1 ft. AMH - Downstream Manhole, Survey Ends - 21 032459.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
59.1SAP
0AMH21 0325
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
59.1AMH21 0324
6.6SAP
0MWM
59.1SRV
7.2SRV

Properties (5)

additional_info
SC306464
custom_field_two
2
customer
LACSD
datetime
2016-12-29T22:39:14-08:00
is_lateral_inspection