Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 28, 2018, 10:23 AM
  • 14 1107_14 1106_08282018_032403.mp4

Date
08/28/2018
W/O
724009
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26059
Time
3:23 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6019
Sewer Name
14 WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_724009_TV14056_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Square
Height
24 in.
Width
24 in.
Upstream MH
14 1107
Downstream MH
14 1106
Dir. of Survey
Downstream
Length Surveyed
256.1 ft.
Total Length
256.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2S00
O&M Rating
200
Overall Index
2
Overall Quick
Overall Rating
200
Pipe schematic from manhole 14 1107 to 14 1106
MH: 14 1107MH: 14 1106downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 11070 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK.,2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start74.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"126.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"176.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"224.5 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"253.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish253.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish256.1 ft. AMH - Downstream Manhole, Survey Ends - 14 1106

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
253.9DAE
0MWL
0MWM
176.3TFA
253.9DAGS
74.4TFA
126.4TFA
0AMH14 1107
224.5TFA
2DAE
256.1AMH14 1106
0MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK.,
2DAGS

Properties (5)

additional_info
SC364783
custom_field_two
4
customer
LACSD
datetime
2018-08-28T03:23:42-07:00
year_laid
40175