Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2018, 08:25 AM
  • 14 1120_14 1119_08292018_012559.mp4

Date
08/29/2018
W/O
724009
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26072
Time
1:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6020
Sewer Name
14 WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_724009_TV14056_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1120
Downstream MH
14 1119
Dir. of Survey
Downstream
Length Surveyed
323.9 ft.
Total Length
323.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Y00
O&M Rating
256
Overall Index
2
Overall Quick
Overall Rating
256
Pipe schematic from manhole 14 1120 to 14 1119
MH: 14 1120MH: 14 1119downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 11200 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start322.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish322.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323.9 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK323.9 ft. AMH - Downstream Manhole, Survey Ends - 14 1119

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
0AMH14 1120
322.7DAE
323.9MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
2DAE
322.7DAGS
2DAGS
323.9AMH14 1119

Properties (5)

additional_info
SC364784
custom_field_two
4
customer
LACSD
datetime
2018-08-29T01:25:40-07:00
year_laid
40175