Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 29, 2018, 10:54 AM
  • 14 1127_14 1126_08292018_035444.mp4

Date
08/29/2018
W/O
724009
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01179
PipeID
P26079
Time
3:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6020
Sewer Name
14 WEST SIDE RELIEF TRUNK
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_724009_TV14056_SEP2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 1126
Downstream MH
14 1127
Dir. of Survey
Upstream
Length Surveyed
106 ft.
Total Length
106 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2G00
O&M Rating
84
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole 14 1126 to 14 1127
MH: 14 1126MH: 14 1127upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 11270 ft. MGO - General Observation - CAPPED CONNECTION AT MH 12 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish104 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start104 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start106 ft. MWM - Water Mark, 25 %of cross sectional area106 ft. AMH - Downstream Manhole, Survey Begins - 14 1126106 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
2DAGS
106AMH14 1127
106MGOCAPPED CONNECTION AT MH 12 O'CLOCK
106MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
0AMH14 1126
2DAE
106DAGS
0MWL
106DAE

Properties (5)

additional_info
SC364784
custom_field_two
4
customer
LACSD
datetime
2018-08-29T03:54:41-07:00
year_laid
40175