Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2018, 04:47 PM
  • H 1341B 0219 District 15_101918.mp4

Date
10/19/2018
W/O
723967
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00085
PipeID
P08801
Time
9:47 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5916
Sewer Name
B JOINT OUTFALL B - UNIT 2B
City
SOUTH ELMONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
32
Purpose
Routine Assessment
Project
WO_723967_TV15203_SEP2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
H 1341
Downstream MH
B 0219
Dir. of Survey
Downstream
Length Surveyed
206.5 ft.
Total Length
206.5 ft.
Structural Index
3
Structural Quick
523G
Structural Rating
124
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
129
Pipe schematic from manhole H 1341 to B 0219
MH: H 1341MH: B 0219downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 134112.8 ft. MGO - General Observation - MAG COAT12.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start196.8 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start205.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish205.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish206.5 ft. AMH - Downstream Manhole, Survey Ends - B 0219

Observation photos (1)

  • General Observation - MAG COAT

    12.8 ft. - General Observation - MAG COAT

Observations (9)

DistanceCodeObservation
0MWM
0MWL
205.3SAV
12.8MGOMAG COAT
196.8SRV
206.5AMHB 0219
0AMHH 1341
12.8SAV
205.2SRV

Properties (3)

custom_field_two
2
customer
LACSD
datetime
2018-10-19T09:47:42-07:00