Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2017, 08:16 AM
  • 14 0090_14 0089_30032017_011726.mpg

Date
03/30/2017
W/O
624327
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00577
PipeID
P18105
Time
1:16 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4404
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_624327_TV14017_MAR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0090
Downstream MH
14 0089
Dir. of Survey
Downstream
Length Surveyed
350.1 ft.
Total Length
350.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 14 0090 to 14 0089
MH: 14 0090MH: 14 0089downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 00902 ft. MMC - Material Change, Vitrified clay pipe23.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"51.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: NO100.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"276.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"307.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"342.8 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES350.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK350.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0089

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, at 10 o'clock,  , within 8 inches of joint: NO

    98.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 10 o'clock, , within 8 inches of joint: NO

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    342.8 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
253.5TF
303.2TFC
176.8TFC
350.1MGOCONNECTION AT MH 3 O'CLOCK
2MMC
77.7TFC
350.2AMH14 0089
226.6TFC
342.8CM
0MWM
100.1TF
51.1TFA
98.2DAGS
307.6TFC
0MWL
149.7TFC
276.5TFC
126.9TF
199.3TFC
0AMH14 0090
23.5TFC

Properties (4)

additional_info
SC345163
custom_field_two
4
customer
LACSD
datetime
2017-03-30T01:16:55-07:00