Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 11, 2017, 05:07 AM
  • 18 0033_18 0032 _10072017_220806.mp4

Date
07/10/2017
W/O
641208
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00713
PipeID
P13849
Time
10:07 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4640
Sewer Name
18 WALNUT WAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
15
Purpose
Routine Assessment
Project
WO_641208_TV18059_JUN2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0032
Downstream MH
18 0033
Dir. of Survey
Upstream
Length Surveyed
319.8 ft.
Total Length
319.8 ft.
Structural Index
3
Structural Quick
3L11
Structural Rating
193
O&M Index
1
O&M Quick
1600
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
199
Pipe schematic from manhole 18 0032 to 18 0033
MH: 18 0032MH: 18 0033upstream0 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 18 00330 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE15.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"30.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"61 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.7 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES82 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"92.1 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES96.9 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES106.7 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES116.3 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES119.8 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES120.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"137.6 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES206 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"283 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"300.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES316.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"316.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start319.8 ft. MWM - Water Mark, 10 %of cross sectional area319.8 ft. MWL - Water Level, 5 %of cross sectional area319.8 ft. AMH - Downstream Manhole, Survey Begins - 18 0032

Observation photos (9)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    182.2 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

    200 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

    203.5 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    213.1 ft. - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

    222.9 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

    227.7 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

    242.1 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
237.8TFC
182.2RFJ
0MWM
198.9TF
227.7RFJ
242.1RFJ
303.9TF
319.8SAV
3.7CM
203.5RFJ
36.8TF
19.5TFC
0MWL
213.1CC
258.8TFC
199.6TFC
3.1TF
222.9RFJ
113.8TF
289.5TFC
3SAV
0AMH18 0032
200RFJ
319.8AMH18 0033
319.8MGOCONNECTION AT MH 9 ACTIVE

Properties (6)

additional_info
SC345386
custom_field_two
3
customer
LACSD
datetime
2017-07-10T22:07:58-07:00
documentation
PROPIPE
is_lateral_inspection
false