Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 25, 2017, 11:07 PM
  • 01 0266A_01 0266_09062017_035701.mp4

Date
05/25/2017
W/O
640730
Weather
Dry
Operator/Surveyor
M. MARTINEZ
Sewer ID
Z00218
PipeID
P01313
Time
4:07 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3968
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_640730_TV01204_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Rectangular
Height
12 in.
Width
12 in.
Upstream MH
01 0266A
Downstream MH
01 0266
Dir. of Survey
Downstream
Length Surveyed
118.4 ft.
Total Length
118.4 ft.
Structural Index
4
Structural Quick
4D00
Structural Rating
92
O&M Index
2
O&M Quick
412D
O&M Rating
50
Overall Index
3
Overall Quick
Overall Rating
142
Pipe schematic from manhole 01 0266A to 01 0266
MH: 01 0266AMH: 01 0266downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 0266A0 ft. MWM - Water Mark, 50 %of cross sectional area1.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: YES, 8"61 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"115.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish115.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish117.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK118.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0266

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    1.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
1.1DAGS
2FM
115.1DAGS
0MWL
0AMH01 0266A
28TF
61TFC
115.1FM
118.4AMH01 0266
117.1MGOCONNECTION AT THE MH 3 O'CLOCK
0MWM

Properties (6)

additional_info
SC342121
custom_field_two
2
customer
LACSD
datetime
2017-05-25T16:07:40-07:00
documentation
PROPIPE
is_lateral_inspection
false