Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2017, 06:58 AM
  • 02 0030_02 0029_21062017_011213.mp4

Date
06/20/2017
W/O
640701
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03061
Time
11:58 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4623
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_640701_TV02341_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0030
Downstream MH
02 0029
Dir. of Survey
Downstream
Length Surveyed
329.1 ft.
Total Length
329.1 ft.
Structural Index
3
Structural Quick
483J
Structural Rating
200
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
202
Pipe schematic from manhole 02 0030 to 02 0029
MH: 02 0030MH: 02 0029downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 003011.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"145.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"245.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.1 ft. RFJ - Roots Fine Joint, from 10 to 11 o'clock, within 8 inches of joint: YESR268.3 ft. RFJ - Roots Fine Joint, from 10 to 02 o'clock, within 8 inches of joint: YESR289.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish289.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start326.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"329.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0029329.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    289.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
148.6TFC
197.4TB
0MWL
252.1RFJ
145.9TF
289.4CM
0MWM
329.1AMH02 0029
11.7CM
289.5FM
329.1FM
0AMH02 0030
31.4TFC
268.3RFJ
326.5TB
245.6TFC

Properties (6)

additional_info
SC345338
custom_field_two
2
customer
LACSD
datetime
2017-06-20T23:58:47-07:00
documentation
PROPIPE
is_lateral_inspection
false