Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 26, 2017, 07:31 AM
  • 02 0006_02 0005A_26062017_005333.mp4

Date
06/26/2017
W/O
640701
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03032
Time
12:31 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4624
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
WO_640701_TV02341_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 0006
Downstream MH
02 0005A
Dir. of Survey
Downstream
Length Surveyed
288.4 ft.
Total Length
288.4 ft.
Structural Index
3
Structural Quick
4139
Structural Rating
31
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
33
Pipe schematic from manhole 02 0006 to 02 0005A
MH: 02 0006MH: 02 0005Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00060 ft. MWL - Water Level, 10 %of cross sectional area5.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start45.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"45.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES52.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start52.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish117.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"195.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"198.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"247.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"284.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish288.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0005A

Observation photos (3)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock,  , within 8 inches of joint: YES

    45.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    52.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
52.5FM
284.4FM
198.4TFA
52.5FL
45.7TFA
45.7DAGS
0MWM
247.6TFC
0AMH02 0006
117.7TFA
195.1TF
0MWL
288.4AMH02 0005A
5.8FL

Properties (6)

additional_info
SC345339
custom_field_two
3
customer
LACSD
datetime
2017-06-26T00:31:17-07:00
documentation
PROPIPE
is_lateral_inspection
false