Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2017, 10:01 AM
  • 18 0250_18 0219 _10072017_030315.mp4

Date
07/10/2017
W/O
640666
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14078
Time
3:01 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4639
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_640666_TV18003_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0250
Downstream MH
18 0219
Dir. of Survey
Downstream
Length Surveyed
315.1 ft.
Total Length
315.2 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 18 0250 to 18 0219
MH: 18 0250MH: 18 0219downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 02500 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE6.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES14.1 ft. CC - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES30.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES51.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES54.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start68.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"146 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"223 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"315.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0219315.2 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE315.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    6.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

    14.1 ft. - Crack Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    30.5 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    51.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    54.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MWL
223TFA
0MWM
54.2CM
0MGOCONNECTION AT MH 9 ACTIVE
6.1CM
0AMH18 0250
68.4TF
51.8CM
315.2AMH18 0219
14.1CC
315.2MGOCONNECTION AT MH 3 ACTIVE
0MGOCONNECTION AT MH 3 ACTIVE
146TF
315.2CM
30.5CL

Properties (6)

additional_info
SC345385
custom_field_two
3
customer
LACSD
datetime
2017-07-10T03:01:21-07:00
documentation
PROPIPE
is_lateral_inspection
false