Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 10, 2017, 08:40 AM
  • 18 0257_18 0256 _10072017_014054.mp4

Date
07/10/2017
W/O
640666
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00672
PipeID
P14085
Time
1:40 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4639
Sewer Name
18 BROADWAY TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_640666_TV18003_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0257
Downstream MH
18 0256
Dir. of Survey
Downstream
Length Surveyed
184.6 ft.
Total Length
184.6 ft.
Structural Index
3
Structural Quick
3C23
Structural Rating
66
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
66
Pipe schematic from manhole 18 0257 to 18 0256
MH: 18 0257MH: 18 0256downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 02570 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE3.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES12.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES20.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES21.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"49.9 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES80.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES93.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start100.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"163.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"184.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish184.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0256

Observation photos (6)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    3.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    12.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    20.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    49.9 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    80.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    93.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
184.6CM
93.9CM
80.3CM
0MGOCONNECTION AT MH 3 ACTIVE
3.6CM
0AMH18 0257
184.6AMH18 0256
20.8CL
163.3TFC
100.3TFC
21.4TFC
12.1CL
49.9CL
0MGOCONNECTION AT MH 9 ACTIVE

Properties (6)

additional_info
SC345385
custom_field_two
3
customer
LACSD
datetime
2017-07-10T01:40:34-07:00
documentation
PROPIPE
is_lateral_inspection
false