Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 22, 2017, 09:23 AM
  • 18 0451_18 0450 _20170522_024329.mp4

Date
05/22/2017
W/O
635635
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00675
PipeID
P14302
Time
2:23 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4501
Sewer Name
18 FLORENCE AVENUE TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
WO_635635_TV18097_MAY2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0450
Downstream MH
18 0451
Dir. of Survey
Upstream
Length Surveyed
316.4 ft.
Total Length
316.4 ft.
Structural Index
3
Structural Quick
423K
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 18 0450 to 18 0451
MH: 18 0450MH: 18 0451upstream0 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK0 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 18 045127.6 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: NO30.3 ft. B - Broken, from 02 to 03 o'clock, within 8 inches of joint: YES57.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"129.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"155.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"258 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"287 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start293.1 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES303.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES304.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.2 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES312.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES316.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK316.4 ft. MWL - Water Level, 10 %of cross sectional area316.4 ft. MWM - Water Mark, 20 %of cross sectional area316.4 ft. MGO - General Observation - HEAVY STEAM FROM PIPE316.4 ft. AMH - Downstream Manhole, Survey Begins - 18 0450

Observation photos (7)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    3.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    8.2 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    13.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    23.3 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    29.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 02 to 03 o'clock, within 8 inches of joint: YES

    286.1 ft. - Broken, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: NO

    288.8 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: NO

Observations (26)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
135.6TFC
109.6TFC
258.9TFC
8.2CL
84.2TFC
12.3TFC
58.4TFC
316.4MGOCONNECTION AT MH 12 O'CLOCK
29.4CM
187.1TFC
0MWL
286.1B
0MWM
161.3TFC
232.8TFC
316.4CM
316.4AMH18 0451
33TFC
23.3CM
13.2CM
0MGOHEAVY STEAM FROM PIPE
3.7CL
207.5TFC
288.8FM
0AMH18 0450

Properties (6)

additional_info
SC345311
custom_field_two
2
customer
LACSD
datetime
2017-05-22T02:23:12-07:00
documentation
PROPIPE
is_lateral_inspection
false