Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2016, 08:07 AM
  • 02 1406_02 1405_20160509_012100.mp4

Date
05/09/2016
W/O
568667
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02977
Time
1:07 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3367
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_568667_TV02220_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
02 1406
Downstream MH
02 1405
Dir. of Survey
Downstream
Length Surveyed
332.6 ft.
Total Length
332.6 ft.
Structural Index
4
Structural Quick
5132
Structural Rating
11
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 1406 to 02 1405
MH: 02 1406MH: 02 1405downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12 14062.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. LR - Alignment Right, 15 %296.5 ft. LL - Alignment Left, 15 %327.3 ft. SRP - Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO327.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish327.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish332.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1405

Observation photos (4)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Alignment Right, 15 %

    2.1 ft. - Alignment Right, 15 %

  • Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO

    327.3 ft. - Surface Reinforcement Projecting, at 12 o'clock, within 8 inches of joint: NO

Observations (11)

DistanceCodeObservation
296.5LL
0MWM
0MWL
327.3SRP
327.3SRV
0AMH12 1406
2.1SRV
332.6AMH02 1405
327.3SAP
2.1SAP
2.1LR

Properties (6)

additional_info
SC300364
custom_field_two
2
customer
LACSD
datetime
2016-05-09T01:07:21-07:00
documentation
PROPIPE
is_lateral_inspection
false