Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 8, 2017, 07:51 AM
  • C 0346_03 0020_08082017_010727.mp4

Date
08/08/2017
W/O
646534
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00366
PipeID
P05247
Time
12:51 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4678
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_646534_TV03011_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
03 0020
Downstream MH
C 0346
Dir. of Survey
Upstream
Length Surveyed
245.4 ft.
Total Length
245.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 03 0020 to C 0346
MH: 03 0020MH: C 0346upstream0 ft. AMH - Upstream Manhole, Survey Ends - C 03460 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0.9 ft. MGO - General Observation - SLIDE GATE119.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 4"241.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start245.4 ft. MWM - Water Mark, 20 %of cross sectional area245.4 ft. AMH - Downstream Manhole, Survey Begins - 03 0020245.4 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
245.4AMHC 0346
3.6DAGS
0MWM
244.5MGOSLIDE GATE
0AMH03 0020
245.4DAGS
0MWL
126.1TB

Properties (6)

additional_info
SC345616
custom_field_two
4
customer
LACSD
datetime
2017-08-08T00:51:47-07:00
documentation
PROPIPE
is_lateral_inspection
false