Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 27, 2017, 07:12 PM
  • 03 0077_03 0076_16082017_093902.mp4

Date
07/27/2017
W/O
1590881
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00366
PipeID
P05099
Time
12:12 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3993
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
05
Purpose
Routine Assessment
Project
WO_646534_TV03011_JUL2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
03 0077
Downstream MH
03 0076
Dir. of Survey
Downstream
Length Surveyed
358.5 ft.
Total Length
358.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
142
Pipe schematic from manhole 03 0077 to 03 0076
MH: 03 0077MH: 03 0076downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 00770 ft. MWM - Water Mark, 40 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"50.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"125.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"221 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"318.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES318.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"318.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish320 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start357 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish358.5 ft. AMH - Downstream Manhole, Survey Ends - 03 0076

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    318.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    320 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
0AMH03 0077
39TFC
221TF
2.1DAGS
125.1TFC
320DAGS
318.1DAGS
358.5AMH03 0076
50.1TB
0MWM
318.1TF
357DAGS
318.1DAGS

Properties (6)

additional_info
SC345560
custom_field_two
4
customer
LACSD
datetime
2017-07-27T12:12:29-07:00
documentation
PROPIPE
is_lateral_inspection
false