Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 17, 2017, 10:28 AM
  • J 0192_J 0191 _07172017_041211.mp4

Date
07/17/2017
W/O
641001
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00055
PipeID
P11431
Time
3:28 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4709
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
SAN PEDRO
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47A
Purpose
Routine Assessment
Project
WO_641001_TV05283_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0192
Downstream MH
J 0191
Dir. of Survey
Downstream
Length Surveyed
578 ft.
Total Length
578 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2V00
O&M Rating
230
Overall Index
2
Overall Quick
Overall Rating
234
Pipe schematic from manhole J 0192 to J 0191
MH: J 0192MH: J 0191downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 01920 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start143.1 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES174.3 ft. CS - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES578 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish578 ft. AMH - Downstream Manhole, Survey Ends - J 0191

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    174.3 ft. - Crack Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
578DAGS
0AMHJ 0192
143.1CS
2DAGS
0MWL
174.3CS
0MWM
578AMHJ 0191

Properties (6)

additional_info
SC345442
custom_field_two
4
customer
LACSD
datetime
2017-07-17T03:28:52-07:00
documentation
PRO PIPE
is_lateral_inspection
false