Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2017, 05:35 AM
  • 18 0208_18 0207 _20170420_225648.mp4

Date
04/20/2017
W/O
624437
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00695
PipeID
P14033
Time
10:35 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4510
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0208
Downstream MH
18 0207
Dir. of Survey
Downstream
Length Surveyed
145.3 ft.
Total Length
145.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4222
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 18 0208 to 18 0207
MH: 18 0208MH: 18 0207downstream0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02080 ft. MWL - Water Level, 55 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 70%13.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start94 ft. MCU - Camera Underwater145.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish145.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0207

Observations (8)

DistanceCodeObservation
145.3DAGS
145.3AMH18 0207
0MWM
2MGOMAG COAT 70%
0AMH18 0208
94MCU
0MWL
13.1DAGS

Properties (6)

additional_info
SC340724
custom_field_two
4
customer
LACSD
datetime
2017-04-20T22:35:47-07:00
documentation
PROPIPE
is_lateral_inspection
false