Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2017, 08:58 AM
  • 18 0213_18 0212 _20170307_021015.mp4

Date
03/07/2017
W/O
624437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00695
PipeID
P14038
Time
12:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4370
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0213
Downstream MH
18 0212
Dir. of Survey
Downstream
Length Surveyed
301.6 ft.
Total Length
301.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
180
O&M Index
2
O&M Quick
412K
O&M Rating
126
Overall Index
3
Overall Quick
Overall Rating
306
Pipe schematic from manhole 18 0213 to 18 0212
MH: 18 0213MH: 18 0212downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 02130 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start53.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.6 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"167.8 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"301.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish301.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0212

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
53.7TB
64.6TFA
301.6DAGS
167.8TBA
0AMH18 0213
64.6TBC
0MWM
0MWL
301.6AMH18 0212
2DAGS

Properties (6)

additional_info
SC306965
custom_field_two
4
customer
LACSD
datetime
2017-03-07T00:58:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false