Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2017, 12:03 PM
  • 18 0193_18 0192 _20170221_051827.mp4

Date
02/21/2017
W/O
624437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00695
PipeID
P14018
Time
4:03 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4246
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
18 0193
Downstream MH
18 0192
Dir. of Survey
Downstream
Length Surveyed
378.7 ft.
Total Length
378.7 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
375
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
525
Pipe schematic from manhole 18 0193 to 18 0192
MH: 18 0193MH: 18 0192downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01930 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start376.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish376.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish378.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE378.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0192

Observation photos (3)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    378.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
2SSS
376.6DAGS
0AMH18 0193
376.6SSS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
378.7MGOCOCKROACHES IN MANHOLE
378.7AMH18 0192
0MWM
2DAGS
0MWL

Properties (6)

additional_info
SC306750
custom_field_two
4
customer
LACSD
datetime
2017-02-21T04:03:07-08:00
documentation
PRO PIPE
is_lateral_inspection
false