Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2017, 09:58 AM
  • 18 0200_18 0199 _20170221_031312.mp4

Date
02/21/2017
W/O
624437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00695
PipeID
P14025
Time
1:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4246
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0200
Downstream MH
18 0199
Dir. of Survey
Downstream
Length Surveyed
300.4 ft.
Total Length
300.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
413H
O&M Rating
140
Overall Index
3
Overall Quick
Overall Rating
140
Pipe schematic from manhole 18 0200 to 18 0199
MH: 18 0200MH: 18 0199downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 02002 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT 70%78.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS300 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish300 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish300.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE300.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0199

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    300.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
300DAGS
0MWM
300.4MGOCOCKROACHES IN MANHOLE
78.5DSZDEBRIS
300DSZ
2DAGS
300.4AMH18 0199
0MWL
0AMH18 0200
2MGOMAG COAT 70%

Properties (6)

additional_info
SC306750
custom_field_two
4
customer
LACSD
datetime
2017-02-21T01:58:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false