Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2017, 10:39 AM
  • 18 0426_18 0173_20170322_041922.mp4

Date
03/22/2017
W/O
624437
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00695
PipeID
P13998
Time
3:39 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4415
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
19
Purpose
Routine Assessment
Project
WO_624437_TV18043_MAR2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
18 0426
Downstream MH
18 0173
Dir. of Survey
Downstream
Length Surveyed
290.7 ft.
Total Length
290.7 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
2
O&M Quick
412K
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
294
Pipe schematic from manhole 18 0426 to 18 0173
MH: 18 0426MH: 18 0173downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 04262 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 50%290.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0173290.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2DAGS
0MWM
0MWL
2MGOMAG COATING 50%
290.7AMH18 0173
0AMH18 0426
290.7DAGS

Properties (6)

additional_info
SC306980
custom_field_two
4
customer
LACSD
datetime
2017-03-22T03:39:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false