Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2016, 05:20 AM
  • 05 1469_05 1468_062016_222345.mpg

Date
06/20/2016
W/O
574372
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00438
PipeID
P06691
Time
10:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3401
Sewer Name
05 EL NIDO TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
23
Purpose
Routine Assessment
Project
WO_574372_TV05300_JUNE2016
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
05 1469
Downstream MH
05 1468
Dir. of Survey
Downstream
Length Surveyed
320.2 ft.
Total Length
320.2 ft.
Structural Index
3
Structural Quick
3W2K
Structural Rating
484
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
484
Pipe schematic from manhole 05 1469 to 05 1468
MH: 05 1469MH: 05 1468downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 14692.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"7.7 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start26.5 ft. CM - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES29.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start61.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"315.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish315.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish315.3 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish320.2 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 3 O'CLOCK320.2 ft. AMH - Downstream Manhole, Survey Ends - 05 1468

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    7.7 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    26.5 ft. - Crack Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    29.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    315.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

    315.3 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish

Observations (21)

DistanceCodeObservation
0MWM
26.5CM
0MWL
258.5TFC
320.2MGOCONNECTION AT THE MH CAPPED 3 O'CLOCK
320.2AMH05 1468
315.3SAP
162.9TFC
2.9SAP
7.7SSS
29.7CM
0MGOCONNECTION AT THE MH 3 O'CLOCK
315.3CM
61.3TFC
315.3SSS
0AMH05 1469
112.2TFC
7.2TFC
160.3TFC
308.8TFC
210.9TFC

Properties (6)

additional_info
SC305851
custom_field_two
2
customer
LACSD
datetime
2016-06-20T22:20:34-07:00
documentation
PROPIPE
is_lateral_inspection
false