Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 23, 2017, 08:21 AM
  • B 0956_B 0037_8232017_045951.mp4

Date
08/23/2017
W/O
0658570
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00113
PipeID
P09418
Time
1:21 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0621
Sewer Name
B JOINT OUTFALL B - UNIT 9A
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Routine Assessment
Project
20170823MDM_JOINT_OUTFALL_B_UNIT_9A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Upstream MH
B 0956
Downstream MH
B 0037
Dir. of Survey
Downstream
Length Surveyed
609.6 ft.
Total Length
609.6 ft.
Structural Index
3
Structural Quick
3322
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole B 0956 to B 0037
MH: B 0956MH: B 0037downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:55AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area8 ft. MGO - General Observation - 78" RCP19.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC42.4 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG79.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE123 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC141 ft. MGO - General Observation - 78" RCP141 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE297.7 ft. MGO - General Observation - 78" RCP500 ft. MGO - General Observation - 78" RCP574 ft. MGO - General Observation - 78" RCP574.5 ft. MGO - General Observation - ZOOM 35'609.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC609.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE609.6 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (11)

  • General Observation - 78" RCP

    8 ft. - General Observation - 78" RCP

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    19.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG

    42.4 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    79.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    123 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • General Observation - 78" RCP

    141 ft. - General Observation - 78" RCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

    141 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE

  • General Observation - 78" RCP

    297.7 ft. - General Observation - 78" RCP

  • General Observation - 78" RCP

    500 ft. - General Observation - 78" RCP

  • General Observation - 78" RCP

    574 ft. - General Observation - 78" RCP

  • General Observation - ZOOM 35'

    574.5 ft. - General Observation - ZOOM 35'

Observations (17)

DistanceCodeObservation
500MGO78" RCP
609.6AMH5:30AM
79.6SSSPEELING CONCRETE
297.7MGO78" RCP
574MGO78" RCP
609.2SAPSEVERE AGG SPORATIC
0AMH4:55AM
141MGO78" RCP
0MWL
0MWM
8MGO78" RCP
609.2SSSPEELING CONCRETE
123SAPSEVERE AGG SPORATIC
141SSSPEELING CONCRETE
574.5MGOZOOM 35'
19.2SAPSEVERE AGG SPORATIC
42.4SAPSEVERE AGG

Properties (6)

custom_field_three
SEVERE AGG PROJECTING SPORATIC
custom_field_two
3
customer
LACSD
datetime
2017-08-23T01:21:58-07:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false