Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2017, 07:36 AM
  • 01 0265_01 0264_15062017_005643.mp4

Date
06/15/2017
W/O
640730
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00218
PipeID
P01311
Time
12:36 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3971-SC342128
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_640730_TV01204_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0265
Downstream MH
01 0264
Dir. of Survey
Downstream
Length Surveyed
337.8 ft.
Total Length
337.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
4124
O&M Rating
12
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 01 0265 to 01 0264
MH: 01 0265MH: 01 0264downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02650 ft. MWL - Water Level, 10 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES5.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start151.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"178.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"242.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"329.4 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 05 to 07 o'clock - UNKNOWN UNDER FLOW337.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish337.7 ft. MGO - General Observation - CONNECTION AT MH 3 OCLOCK337.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0264

Observation photos (2)

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    2.4 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    5.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
337.7MGOCONNECTION AT MH 3 OCLOCK
178.8TF
337.8AMH01 0264
0MWM
2.4DAGS
242.6TF
151.5TF
329.4OBZUNKNOWN UNDER FLOW
0AMH01 0265
0MWL
337.4DAGS
5.6DAGS

Properties (4)

custom_field_two
4
customer
LACSD
datetime
2017-06-15T00:36:03-07:00
lining
CIPP