Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2016, 10:39 AM
  • 02 1394_02 1393_20160510_040121.mp4

Date
05/10/2016
W/O
568667
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00349
PipeID
P02965
Time
3:39 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3369
Sewer Name
02 DISTRICT #2 INTERCEPTOR TRUNK
City
BELL GARDENS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_568667_TV02220_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
54 in.
Upstream MH
02 1394
Downstream MH
02 1393
Dir. of Survey
Downstream
Length Surveyed
656.9 ft.
Total Length
656.9 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1394 to 02 1393
MH: 02 1394MH: 02 1393downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13940.2 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start647.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish656.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1393

Observation photos (1)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start

Observations (6)

DistanceCodeObservation
647.3SRV
0MWL
0AMH02 1394
656.9AMH02 1393
0.2MWM
2.1SRV

Properties (4)

additional_info
SC300367
custom_field_two
2
customer
LACSD
datetime
2016-05-10T03:39:48-07:00