Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2017, 06:16 AM
  • 16 0561_16 0560 _27092017_231920.mp4

Date
09/27/2017
W/O
663060
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13612
Time
11:16 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4279
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_663060_TV16078_OCT2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
22 in.
Width
22 in.
Upstream MH
16 0561
Downstream MH
16 0560
Dir. of Survey
Downstream
Length Surveyed
310.7 ft.
Total Length
310.7 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
183
O&M Index
2
O&M Quick
2K11
O&M Rating
123
Overall Index
2
Overall Quick
Overall Rating
306
Pipe schematic from manhole 16 0561 to 16 0560
MH: 16 0561MH: 16 0560downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 16 05610 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. VC - Vermin Cockroach2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAG COAT START106.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"199.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"286.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"306.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish306.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish306.3 ft. MGO - General Observation - MAG COAT FINISH310.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0560

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
286.4TFA
310.7AMH16 0560
2.1DAGS
2.1SAV
199.1TFA
306.3SAV
306.3MGOMAG COAT FINISH
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
2.1MGOMAG COAT START
0AMH16 0561
0MWM
0VC
306.2DAGS
106.2TFA

Properties (4)

additional_info
SC352124
custom_field_two
3
customer
LACSD
datetime
2017-09-27T23:16:18-07:00