Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2017, 09:13 AM
  • 16 0554_16 0553 _28092017_021409.mp4

Date
09/28/2017
W/O
663060
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13605
Time
2:13 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4279
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_663060_TV16078_OCT2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
16 0554
Downstream MH
16 0553
Dir. of Survey
Downstream
Length Surveyed
217.2 ft.
Total Length
217.2 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
126
O&M Index
2
O&M Quick
2G00
O&M Rating
84
Overall Index
3
Overall Quick
Overall Rating
210
Pipe schematic from manhole 16 0554 to 16 0553
MH: 16 0554MH: 16 0553downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 05540 ft. MWM - Water Mark, 20 %of cross sectional area3.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.1 ft. MGO - General Observation - MAG COAT START3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"81.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"145.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"169.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"202.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"205.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"215.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish215.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish215.4 ft. MGO - General Observation - MAG COAT FINISH217.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0553, VERMIN

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
145.1TFC
202.8TFA
3.1DAGS
215.4SAV
217.2AMH16 0553, VERMIN
205.9TFC
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
0MWL
215.4DAGS
3.1MGOMAG COAT START
0AMH16 0554
3.1SAV
215.4MGOMAG COAT FINISH
24.8TFA
169.7TFA
81.1TFA
0MWM

Properties (4)

additional_info
SC352124
custom_field_two
3
customer
LACSD
datetime
2017-09-28T02:13:53-07:00