Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 9, 2015, 06:57 AM
  • 16 0615_16 0614_20151208_231958.mp4

Date
12/08/2015
W/O
531059
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00664
PipeID
P13665
Time
10:57 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2843
Sewer Name
16 PASADENA EAST-WEST INTERCEPTOR TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
09
Purpose
Routine Assessment
Project
WO_531059_TV16030_OCT2015
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
16 0615
Downstream MH
16 0614
Dir. of Survey
Downstream
Length Surveyed
647 ft.
Total Length
647 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
1
O&M Quick
2213
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
13
Pipe schematic from manhole 16 0615 to 16 0614
MH: 16 0615MH: 16 0614downstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 16 06150 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2.5 ft. MGO - General Observation - MAGNEZIUM H.O. START2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start204.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"269.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"310 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"389 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"444.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"444.8 ft. VC - Vermin Cockroach454.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"510.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS INSIDE LIGHT642.9 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH642.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish642.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish647 ft. AMH - Downstream Manhole, Survey Ends - 16 0614647 ft. VC - Vermin Cockroach647 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
510.3TFDEBRIS INSIDE LIGHT
0MGOLATERAL AT MH 9 OCLOCK ACTIVE
0AMH16 0615
444.8TF
389TFA
310TFC
642.9MGOMAGNEZIUM H.O. FINISH
647AMH16 0614
0VC
642.9DAGS
0MWL
0MWM
269.1TFC
2.5MGOMAGNEZIUM H.O. START
647VC
444.8VC
454.2TFA
2.5DAGS
642.9SAV
647MGOLATERAL AT MH 9 OCLOCK ACTIVE
2.5SAV
204.9TFC

Properties (4)

additional_info
SC205697
custom_field_two
3
customer
LACSD
datetime
2015-12-08T22:57:26-08:00