Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2017, 09:42 AM
  • 05 1270_05 1269 _20062017_035950.mp4

Date
06/20/2017
W/O
640992
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00518
PipeID
P06482
Time
2:42 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3974-SC342132
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_640992_TV05332_JUN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1270
Downstream MH
05 1269
Dir. of Survey
Downstream
Length Surveyed
335.6 ft.
Total Length
335.6 ft.
Structural Index
3
Structural Quick
413H
Structural Rating
136
O&M Index
2
O&M Quick
5242
O&M Rating
154
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 05 1270 to 05 1269
MH: 05 1270MH: 05 1269downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 12706.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start33.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES62.7 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, #v, within 8 inches of joint: YES, 6", 5"62.7 ft. RML - Roots Medium Lateral, at 11 o'clock, 5 %, within 8 inches of joint: YES79.3 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, #v, within 8 inches of joint: YES, 6", 10"112.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start149.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"169.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6"220.4 ft. RBL - Roots Ball Lateral, at 11 o'clock, 80 %, within 8 inches of joint: YES220.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"224.3 ft. TBI - Tap Break-In Intruding, at 01 o'clock, -, #v, within 8 inches of joint: YES, 6", 10"255.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"283.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"332.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish335.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK335.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1269

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    6.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    33.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    112.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Ball Lateral, at 11 o'clock, 80 %, within 8 inches of joint: YES

    220.4 ft. - Roots Ball Lateral, at 11 o'clock, 80 %, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
62.7TBI
255.8TFC
79.3TBI
220.4RBL
0MWL
333.1DAGS
332.8CM
169.3TB
112.3CM
0MWM
220.4TF
62.7RML
335.2MGOCONNECTION AT THE MH 9 O'CLOCK
283.6TFC
6.1DAGS
33.9FM
149.3TFC
0AMH05 1270
224.3TBI
335.6AMH05 1269

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-06-20T02:42:32-07:00